Tempering Valves TVI521319AUSS
Australian Standards approved thermostatic valve with 20mm 90° isolator unions
For multi point of use applications only
Minimum flow rate for stable operation: 4L/min
Recommended working pressure: 100 – 500kPa (balanced)
Kv = 28L/min
Union connectors with o-ring seal with hot and cold check valves
Temperature range adjustable: 30 – 50°C
Temperature control: +/- 3°C
Max. operating temperature: 85°C
Body in dezincification resistant brass
In wall polished Stainless steel box with hinged door and lock
Dimensions 300x300x70mm
Conditional guarantee: 5 years parts and labour